Output voltage and frequency(2)
pure sine wave 230 Vac (± 2%) / 120 Vac(3) and 45-65 Hz(3) ± 0.05% (crystal controlled)
Consumption OFF/Stand-by/ON
1.1/1.4/7 W
1.2/1.5/8 W
1.3/1.6/8 W
The 3 models reach up to 93% of maximum efficiency | Maximum load up to short-circuit | Asymmetric load up to pcont. | Load detection (stand-by) (2) 2 to 25 W | Cos φ 0.1-1 | Harmonic distortion < 2 % | Overload and short-circuit protection automatic disconnection with 3 time restart attempt | Overheat protection warning before shut-off – with automatic restart
Maximum charging current(2) |
35 A
25 A
12 A
Charge characteristic(2) 6 steps: bulk, absorption, floating, equalization, reduced floating, periodic absorption | Temperature compensation(2) with bts 01 or bsp 500/1200 | Power factor correction (PFC) EN 61000-3-2
Input voltage and frequency (2) |
150 to 265 Vac / 50 to 140 Vac (3) and 45 to 65 Hz
16 Aac / 20 Aac
Transfer time
< 15 ms
Weight |
8.2 kg
9 kg
9.3 kg
Dimensions h/w/l [mm] |
110/210/310 mm
Conformity
low voltage directive (LVD) 2014/35/EU: EN/IEC 62477-1, 62109-1, 62109-2, 62040-1, electromagnetic compliance (EMC) directive 2014/30/EU: EN/IEC 61000-3-2, 61000-3-3, 61000-6-2, 61000-6-4, 62040-2